HVACLoadCalc

Duct CFM: the BTU ÷ (ΔT × 1.08) guide

One formula turns equipment size into the airflow your ducts must carry — with the worked numbers for every common system size.

The formula

CFM = BTU/hr ÷ (ΔT × 1.08). The 1.08 constant is air's heat-carrying capacity at sea level (0.075 lb/cu ft density × 0.24 BTU/lb-°F × 60 min/hr). ΔT is the temperature split between supply and return air — the amount the equipment heats or cools the air in one pass.

Worked example: a 2-ton (24,000 BTU/hr) AC at a typical cooling ΔT of 27–28°F: CFM = 24,000 ÷ (28 × 1.08) ≈ 794 CFM — which is exactly where the industry shorthand of ~400 CFM per ton comes from. Setups with a smaller split (20°F) run more CFM per ton; drier-coil designs with a bigger split run less. Your equipment's spec sheet and measured split settle it.

CFM by tonnage, at the usual ΔTs

SystemΔT 20°FΔT 25°FΔT 30°F
1.5 ton (18,000 BTU/hr)833667556
2 ton (24,000 BTU/hr)1,111889741
2.5 ton (30,000 BTU/hr)1,3891,111926
3 ton (36,000 BTU/hr)1,6671,3331,111
4 ton (48,000 BTU/hr)2,2221,7781,481
5 ton (60,000 BTU/hr)2,7782,2221,852

Heating with a gas furnace? ΔT is much larger — 40–60°F is normal, so a 60,000 BTU/hr furnace at ΔT 50 needs only 1,111 CFM. Heat pumps sit near 20–25°F in heating.

Per-run airflow

Divide total CFM by the number of supply runs to sanity-check the branch layout. At 1,200 CFM across 8 runs, each branch carries 150 CFM — typical residential branches at 6–7 inch round carry 100–150 CFM. If your per-run number forces 8-inch branches everywhere, the trunk is starved or the run count is too low.

Duct (round, typical residential)Carries, approx CFM
5 inch branch60–80
6 inch branch100
7 inch branch150
8 inch branch200
12 inch trunk800–1,000
14 inch trunk1,200–1,400

Diagnosing an existing system

Measure supply and return temps a few feet from the equipment with a probe thermometer. Cooling split much under 16°F usually means low airflow (dirty coil/filter, undersized returns); much over 22°F on AC suggests low charge or, in humid climates, deliberately low airflow for dehumidification. The formula runs both directions — measured CFM × ΔT × 1.08 gives you delivered BTU/hr.

Affiliate

Measuring your own system: a dual-probe thermometer, a vane anemometer for register velocity, and a static-pressure manometer are the three tools techs actually use.

Honest label: CFM is the airflow target, not a duct design. Sizing actual ducts — friction rates, equivalent lengths, available static pressure — is ACCA Manual D territory, and blower specs must match the external static pressure of your system. Use these numbers to plan and sanity-check, not to cut sheet metal.

Size the equipment first in the HVAC load calculator, then work its BTU through the CFM calculator above.